Condition assessment



The type of cable and the nature of the most common defects within it will determine the most effective diagnostic method to apply.
Possible diagnostic methods include:
  • Dielectric spectroscopy (for water trees)
  • Leakage current detection (for contamination, large defects in paper cables systems) 
  • Loss-factor measurement (for water trees and some other defects)
  • PD tests (for many different types of defects, as long as they generate partial discharges)
    o  Off-line with an 0.1 Hz source
    o  Off-line with a 50 Hz source
    o  Off-line with an OWTS (Oscillating Wave Test System) source
    o  On-line



Applying an effective diagnostic method will normally result in a recommendation, for instance immediate repair, repair within one year, repeat measurement after 1-2 years, or no further action needed.